With our successful modification CSIE provided a schematic design expansion to double the tenant’s IT capacity, rated at 30 KW per processing cabinet (over 500 KW) within their existing suite with liquid cooling supported for the application. Let us engineer your network in a complimentary and business strategic method to maximize value. We combine fiber-rich, carrier-neutral data centers with industry-leading SLAs to deliver low latency, secure connectivity solutions.

By implementing the recommendations, Element Critical was able to eliminate this CRAC unit and increase the leasable space within the room. You need a data center partner with a wide array of options. To compensate the client had added a 97-ton CRAC unit in the adjacent suite to capture the room over temperature conditions and keep the environment within control. This technology would also be implemented in Element Criticals planned high density applications.Īt the point of CSIE’s involvement the room was over heating and the refrigerant door solution was not able to neutralize the load.

CSIR recommended an improvement to the current refrigerated door solution, with an increased heat transfer and door capacity and additional redundancy. CSIE provided an engineering evaluation of this data center co-location facility to correct an existing cooling deficiency and future cooling requirements.